Aktuelle Forschungsprojekte

Image Micro fluidic expansion valve
Image Tribological investigations of oil-refrigerant-material-systems
Image 3D - Air flow sensor
Image Behavior of multiphase cryogenic fluids
Image Multifunctional electronic modules for cryogenic applications
Image Influenced melting point of water by magnetic field
Image Solar Cooling
Image Preformance measurements of heat exchangers
Image Modular storage system for solar cooling
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image Thermostatic Expansion Valves
Image Electrical components in refrigeration circuits
Image Lifetime prediction of hermetic compressor systems
Image High temperature heat pump
Image Helium extraction from natural gas
Image Innovative Manufacturing Technologies for Cryosorption Systems

You are here:  Home /  Measurements and Tests


Development of test methods and test rigs for stationary integrated refrigeration units

BMWi Euronorm Innokom

02/2017 – 07/2019

Andreas Peusch

+49-351-4081-5221

How efficient is my refrigeration unit?

The objective of the R&D project was the development of a test method for stationary integrated refrigeration units. The test method comprises different device variants, like ceiling mounted, wall mounted or split refrigeration units. The method provides reliable performance data and thus enables a manufacturer-independent efficiency comparison.

Measurements in the 3- or 4-chamber measurement setup were carried out using the calorimeter method with compensation of the ambient conditions. This enabled the measurements of devices with low cooling capacity (0.5 - 4 kW).

In the selected test setup (Figure 1), the cooling capacity is measured indirectly via an electrical power of the compensation heating. To determine the total cooling capacity, the heat input into the calorimeter room and, if necessary, internal loads (sensible and latent heat) have to be added together.

The test method comprises following features:

  • Suitable for low temperature devices (-20 °C) and normal temperature cooling (0 °C)
  • Measurement in the calorimeter room (3- or 4-zone concept)
  • Determination of heat input via enclosure surfaces before power measurement
  • Establishment of equilibrium conditions (settling phase) of the temperatures to be set (up to 24 h)
  • Measuring period up to 6 h with permissible tolerance band of 0.2 K

Conclusion:

  • Results were included in new test standard prEN 17432
  • Establishment of a uniform Europe-wide comparison criterion
  • Performance and efficiency data on a uniform basis leads to higher confidence and thus also to lower consumption costs