Aktuelle Forschungsprojekte

Image Low Temperature Measuring Service
Image Thermostatic Expansion Valves
Image Reduction of primary noise sources of fans
Image Software modules
Image Software for technical building equipment
Image Corrosion inhibitor for ammonia absorption systems
Image High Capacity Pulse Tube Cooler
Image Preformance measurements of heat exchangers
Image 3D - Air flow sensor
Image Cold meter
Image Low noise and non metallic liquid-helium cryostat
Image Helium extraction from natural gas
Image Calibration leak for the water bath leak test
Image Low Temperature Tribology
Image Lifetime prediction of hermetic compressor systems
Image Industry 4.0 membrane heat and mass exchanger (i-MWÜ4.0)

You are here:  Home /  Software Development


Reducing the filling quantity

BMWi EuroNorm INNO-KOM

03/2019-06/2021

K. Bratanitsch

+49-351-4081-5212

How much refrigerant must be filled?

Due to the F-gas regulation of the EU, synthetic refrigerants are becoming increasingly expensive and more difficult to obtain. The synthetic and partly natural substitute refrigerants are often flammable or toxic. The remaining synthetic refrigerants with low hazard potential are becoming more and more expensive and some of them still have a significant global warming potential. For this reason, it makes sense to keep the filling quantity of all new refrigeration systems as low as possible. Historically, refrigeration plants have usually been built without much consideration for the filling quantity of the plant. Often even large collectors were installed in order to always have a sufficient filling quantity without exact calculation and to compensate for the loss of refrigerant between the service intervals.

In this project, possible actions are investigated, which lead to significant reductions in refrigerant filling quantities already in the design and construction phase. In particular, the necessity and size of refrigerant receivers will be investigated. Except for a refrigerant receiver, the largest refrigerant quantities are found in the heat exchangers of the refrigeration cycle, i.e. in the condenser up to 50 % (according to other literature sources even up to 65 %) and in the evaporator up to 25 %. As a result, very strong levers for reducing the refrigerant charge can be seen in these components. Therefore, the necessary filling quantity of different heat exchangers should be examined and measured in detail. Thereby classical tube-fin, microchannel and plate heat exchangers shall be investigated.

As a result of the project, a new method is to be developed which takes into account a maximum possible reduction of the refrigerant charge quantity from the outset when planning and designing a refrigeration system.

Based on the first results and previous experience we can offer calculations of the filling quantity. Furthermore, a program for calculating the filling quantity is in preparation.

 


Your Request

Further Projects - Software Development

Image

Combined building and system simulation

Scientific analysis of thermodynamic processes in buildings and its systems

Image

Optimizing HVAC operation with machine learning

Intelligent control of HVAC systems – high comfort with low energy demand

Image

Software modules

Software for properties of refrigerants

Image

Software for technical building equipment

Design cooling load and energetic annual simulation (VDI 2078, VDI 6007, VDI 6020)