Aktuelle Forschungsprojekte

Image Tribological investigations of oil-refrigerant-material-systems
Image Panel with indirect evaporative cooling via membrane
Image Behavior of multiphase cryogenic fluids
Image Modular storage system for solar cooling
Image Testzentrum PLWP at ILK Dresden
Image Low noise and non metallic liquid-helium cryostat
Image Pulse-Tube-Refrigerator with sealed compressor
Image Brine (water)-water heat pump
Image Service offer for Leak Detection and Tightness Test
Image Software for test rigs
Image Lifetime prediction of hermetic compressor systems
Image IN-SITU SWELLING BEHAVIOUR OF POLYMER MATERIALS IN FLAMMABLE FLUIDS
Image Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image Laseroptical measurement
Image Cold meter

You are here:   /  Home


Calibration leak for the water bath leak test

EURONORM GmbH

02/2022 - 02/2024

Dipl.-Ing. (FH) René Seidel

+49-351-4081-5428

Kali.f.WaDi

Problem

Various methods are available for leak testing of technical components, especially in refrigeration technology. These include the "bubble detection (immersion)" method (method C1 according to DIN EN 1779), which is widely used in practice. In this method, the test specimen is pressurized with test gas and placed in a basin filled with a test fluid (usually water with additives). Bubbles rising from the leak indicate the leak. This principle is generally known from its use, for example, for leak detection on bicycle inner tubes.

Under optimum conditions, leakage rates of 5 g/a refrigerant can thus be reliably detected. This makes the method suitable for use in refrigeration technology, whose permissible leakage rate is 5 g/a refrigerant (≙ 3x10-5 mbar l/s R1234yf) per connection point.

While a calibration option or at least a functional check is available for almost every technical process (for example, there are various calibration leaks for selective gas sensors on the market), this has not been the case for water bath testing to date. The calibration leaks available on the market to date are not suitable for underwater use.

However, the proof of test process suitability for leak testing by means of water bath testing, which is necessary from a quality management point of view, is hardly possible without a suitable reference or calibration leak.

State of the art

Although the water bath testing method is widely used in the market, no calibration leaks, especially with a leakage rate of < 10-3 mbar l/s, are available in practice as test standards for use in water bath testing. This applies regardless of whether the procedure is used manually or automatically. The leaks available on the market to date may not be immersed or submerged due to their design.

This gap in the market is to be closed within the scope of the project applied for by developing a corresponding calibration leak suitable for water bath testing.

Target

The project goal is to develop calibration leaks for the range of small leakage rates of 5 to 500 g/a refrigerant (corresponding to a leakage rate of approx. 3x10-5 to 3x10-3 mbar l/s R1234yf), i.e. (almost) to the lower detection limit of the water bath test. Converted to air, this corresponds to a volume flow of the order of 0.1 to 10 ml/h (assuming laminar flow).

For the broadest possible applicability, leaks with a predefined, fixed leak rate as well as leaks with a variable leak rate are to be developed.