Aktuelle Forschungsprojekte

Image Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K
Image Filter Tests
Image Cryostats, Non-Metallic and Metallic
Image Software for technical building equipment
Image Computational fluid dynamics CFD
Image Electrochemical decontamination of electrically conducting surfaces „EDeKo II“
Image Investigation of materials
Image Verification of storage suitability of cryo tubes
Image Thermal engines
Image Influenced melting point of water by magnetic field
Image Heat2Power
Image Industry 4.0 membrane heat and mass exchanger (i-MWÜ4.0)
Image Electrical components in refrigeration circuits
Image Combined building and system simulation
Image Investigation of coolants
Image Reduction of primary noise sources of fans

You are here:  Home /  Measurements and Tests


Development of test methods and test rigs for stationary integrated refrigeration units

BMWi Euronorm Innokom

02/2017 – 07/2019

Andreas Peusch

+49-351-4081-5221

How efficient is my refrigeration unit?

The objective of the R&D project was the development of a test method for stationary integrated refrigeration units. The test method comprises different device variants, like ceiling mounted, wall mounted or split refrigeration units. The method provides reliable performance data and thus enables a manufacturer-independent efficiency comparison.

Measurements in the 3- or 4-chamber measurement setup were carried out using the calorimeter method with compensation of the ambient conditions. This enabled the measurements of devices with low cooling capacity (0.5 - 4 kW).

In the selected test setup (Figure 1), the cooling capacity is measured indirectly via an electrical power of the compensation heating. To determine the total cooling capacity, the heat input into the calorimeter room and, if necessary, internal loads (sensible and latent heat) have to be added together.

The test method comprises following features:

  • Suitable for low temperature devices (-20 °C) and normal temperature cooling (0 °C)
  • Measurement in the calorimeter room (3- or 4-zone concept)
  • Determination of heat input via enclosure surfaces before power measurement
  • Establishment of equilibrium conditions (settling phase) of the temperatures to be set (up to 24 h)
  • Measuring period up to 6 h with permissible tolerance band of 0.2 K

Conclusion:

  • Results were included in new test standard prEN 17432
  • Establishment of a uniform Europe-wide comparison criterion
  • Performance and efficiency data on a uniform basis leads to higher confidence and thus also to lower consumption costs