Current research projects

Image Investigation according to DIN EN ISO 14903
Image Investigation of coolants
Image Measurement of insulated packaging
Image Thermostatic Expansion Valves
Image Optimizing HVAC operation with machine learning
Image Lifetime prediction of hermetic compressor systems
Image Modular storage system for solar cooling
Image Investigation of material-dependent parameters
Image Reduction of primary noise sources of fans
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image Helium extraction from natural gas
Image Investigation of materials
Image Software for test rigs
Image Practical training, diploma, master, bachelor
Image Refrigerants, lubricants and mixtures
Image Humidifier System for High-Purity Gases

You are here:   /  Home


Low Temperature Tribology

Industry and R&D

Dipl.-Ing. Gunar Schroeder

+49-351-4081-5129

Tribological studies at cryogenic temperatures

For special applications at cryogenic temperatures the use of dry friction is necessary because the working temperatures are significant lower than the working range of liquid lubricants.

The ILK Dresden has extensive experience in the field of material testing at cryogenic temperatures and has developed a measuring system (from roomtemperature down to cryogenic temperatures) to determine the roughness and the coefficient of friction of different sliding material combinations.

The test stand consists of an experimental platform and a traversing mechanism with a force sensor, which is controlled via PC. The direct measurement of the friction force is carried out by the distance covered. Measurements can be performed down to −196 °C (lower temperatures on request). The cooling of the experimental platform and the samples is realised by a controlled liquid nitrogen heat exchanger/evaporator. Measurements are performed under an atmosphere of gaseous nitrogen to prevent the ingress of moisture. Thereby the experimental samples have no direct contact to liquid nitrogen. The uniform temperature distribution is measured by thermocouples, which are calibrated at the ILK Dresden.

Advantages: modular test setup which can be changed to specific requirements; adjustment of sample geometry and/or test track is possible.

Parameter

Measuring accuracyMeasuring range 0.4 N to 2 N≤ 1 % of measured value
Measuring range 2 N to 100 N≤ 0.5 % of measured value
Measuring range extendible up to 5 kN

Repeatability
(e.g. PTFE)

± 0.05 N respectively 1.5 % of coefficient of friction

Your Request

Further Projects

Image

ZeroHeatPump

Performance management of small heat pumps without energy consumption

Image

Mass Spectrometer

Determining the composition of gas mixtures in the high or ultra-high vacuum range