Aktuelle Forschungsprojekte

Image Influenced melting point of water by magnetic field
Image Verification of storage suitability of cryo tubes
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image Air-flow test rig for fan characteristic measurement
Image Helium extraction from natural gas
Image Innovative Manufacturing Technologies for Cryosorption Systems
Image Multifunctional electronic modules for cryogenic applications
Image Modular storage system for solar cooling
Image Combined building and system simulation
Image Test rigs for refrigeration and heat pump technology
Image Preformance measurements of heat exchangers
Image Humidifier System for High-Purity Gases
Image Software for technical building equipment
Image All-in-one device for freeze-drying and production of biomaterial
Image Calibration leak for the water bath leak test
Image Computational fluid dynamics CFD

You are here:  Home /  Measurements and Tests


Thermostatic Expansion Valves

Industry

Dr.-Ing. Matthias Böhm

+49-351-4081-5211

Does the TXV function correctly?

We support the industry in the development of energy-efficient vapor-compression refrigeration system and compression heat pumps.

The ILK Dresden offers the following services for you:

The ILK Dresden have been active in the field of performance testing of refrigeration compressors and condensing units for over 20 years.

Our offer includes also the investigation of thermostatic expansion valves (TEV) with external temperature sensors.

The tests of the TEV are carried out on a suitable refrigeration cycles (fig. 2), taking into account the following standards

  • AHRI 750 (2007),
  • ANSI/ ASHRAE 17 (2008, fig. 1) and
  • ASERCOM-Statement (9_GER_Dimensionierung_von_TXV_2011)

Current calibrations of the measuring systems are a matter of course.

The test can be carried out with the refrigerants R134a, R404A, R407A, R407C, R407F, R448A, R513A, R452A up to a mass flow of 400 kg/h (~20 kW for R134a).

Additional offerings

The following influences on the valve behaviour can be investigated

  • run-in period
  • hysteresis
  • transient tests / time constant
  • pressure losses
  • sub cooling
  • ambient temperature
  • critical pressure ratio