Current research projects

Image Pulse-Tube-Refrigerator with sealed compressor
Image CFE-Test of Cooker Hoods
Image Cool Up
Image Refrigerants, lubricants and mixtures
Image State of system and failure analyses
Image Software for test rigs
Image Industry 4.0 membrane heat and mass exchanger (i-MWÜ4.0)
Image Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K
Image Ice Slurry Generation
Image Certification of efficient air conditioning and ventilation systems through the new "indoor air quality seal" for non-residential buildings
Image Humidifier System for High-Purity Gases
Image Performance tests of condensing units
Image Combined building and system simulation
Image Characterisation of Superconductors in Hydrogen Atmosphere
Image Modular storage system for solar cooling
Image Low Temperature Tribology

You are here:   /  Home


Humidifier System for High-Purity Gases

Industry and Research Instituts

Moritz Kuhn

+49-351-4081-5120

Nafion - moisture transfer

At the ILK Dresden a humidification system was developed and manufactured which is especially suitable for research facilities where very low dew point temperatures have to be adjusted and at the same time a high gas purity has to be guaranteed. The core component is a PermaPure® humidifier with Nafion® moisture exchange. The humidification system precisely controls the dew point via a bypass mixing with dry gas and also takes over the automatic filling of evacuated containers. The control system is optimised to prevent recondensation. Humidification can be controlled from any plant system via an interface. Table 1 shows the technical data of a humidification system for the humidification of synthetic air realized for the KIT in Karlsruhe. The system can be adapted for other applications, and all parameters can be adjusted to the respective requirements.

Table  1: Technical Data Humidifier System
Parameter Value
setpoint gas flow 750 litre/min
maximum relative humidity 95%
minimum dew point -60°C / -76°F
degree of gas purity 5.0
gas purity, number of particle < 5 particle/cm³

Your Request