Current research projects

Image Cold meter
Image Behavior of multiphase cryogenic fluids
Image Panel with indirect evaporative cooling via membrane
Image High Capacity Pulse Tube Cooler
Image Lifetime prediction of hermetic compressor systems
Image Non- invasive flow measurements
Image Ionocaloric cooling
Image Overall System Optimization of Refrigeration Plant Systems for Energy Transition and Climate Protection
Image High temperature heat pump
Image Hybrid- Fluid for CO2-Sublimation Cycle
Image Industry 4.0 membrane heat and mass exchanger (i-MWÜ4.0)
Image In-Situ-Swelling Behaviour of Polymer Materials in Flammable Fluids
Image Refrigerants, lubricants and mixtures
Image Preformance measurements of heat exchangers
Image Investigation of materials
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures

You are here:   /  Home


Measurements on ceiling mounted cooling systems

Dipl.-Ing. Ralf Noack

+49-351-4081-5219

Comparative performance measurement

Measurements of the cooling capacity and efficiency on ceiling mounted cooling systems

For the cooling of refrigeration chambers and cold rooms are ceiling mounted cooling units from different manufacturers in various output ratings on the market available .To qualify these devices in terms of their technical performance data a test scenario was developed. By this methodology, which are based on the testing standards DIN EN 14511: 2013 for air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling and on the older DIN 8942: 1995 builds for integrated refrigeration units, a direct comparison can be made.The concept for the test methodology was necessary because currently no measurement standard for these device specifications exists. It is to be recognised, that a large discrepancy appears between the data sheet specifications and the measurement results. The amount of the determined deviation, shown in the following table,  is different and depends on the manufacturer.

normal cooling - test conditions 0°C / 32°C
cooling capacityelectrical power
consumption
EER
typedatasheetdeviation to datasheetdatasheetdeviation to datasheetcalc. with
datasheet  values
deviation to datasheett
MSB11334 W-42,9%800 W+ 32,5%1,67-56,9%
SFM11417 W-44,4%854 W- 1,3%1,66-43,7%
CMC11300 W-9,6%950 W- 0,8%1,37-8,8%
MSB24001 W-38,2%2400 W- 3,8%1,67-35,8%
SFM23890 W-40,9%2036 W- 6,7%1,91-36,7%
CMC23300 W-4,3%1740 W+4,7% 1,90-8,6%
SFM32646 W-39,5%1343 W+6,9%1,97-43,4%
MSB32054 W-40,7%1150 W+5,4%1,79-43,7%
GEKN12206 W-3,6%1855 W-3,8%1,19 +0,2%
SFM41342 W-32,8%692 W+9,2%1,94-38,5%
SFM53382 W-35,6%1672 W+2,8%2,02-37,4%
MSB41200 W-100 %730 W-31,6%1,64-100,0 %
GEKN2908 W+12,7%809 W+0,6%1,12+12,0%

For devices for deep freezing, the determined deviations are shown in the table below.

deep freezing - test conditions -20°C / 32°C
cooling capacityelectrical power
consumption
EER
typedatasheetdeviation to datasheetdatasheetdeviation to datasheetcalc. with
datasheet  values
deviation to datasheet
BSB1223 W-52,2%1300* W- 7,0%0,96-49,7%
CMF11300 W-4,8%1420 W+1,5%0,92-6,2%
SFL11258 W-36,5%1239 W+12,7%1,02-43,6%
BSB23471 W-60,3%3800 W-4,2%0,98-58,6%
SFL23497 W-42,4%3061 W+1,6%1,14-43,3%
CMF22900 W-3,1%2680 W+6,3%1,08-8,9%
SFL32142 W-34,5%1564 W+10,2%1,37-40,6%
BSB3855 W-44,1 %700 W+27,1%1,22-56,0%
GEKT11431 W-22,2%2025 W-5,8% 0,71-17,5%
SFL41655 W-36,4%1200 W+14,1%1,38-44,2%
GEKT2826 W-8,8%1054 W+0,2%0,78-9,0%

* shown value = power consumtion of the compressor (no fan and controller consumtion included).
The test methodology was applied to all devices. With several pretest measurements were checked the reproducibility of the results. The variation of the measurement results was significantly below 5%, based on the measured cooling capacityIn addition to our measurements, a device was measured comparing on another teststand outside the ILK. The deviation of the determining cooling capacity between the two test stands was also significantly below 5%. Thus it can be assumed that the test method is suitable for determining device cooling capacities.  The measurement results are representative for the test stand and thus provide a good basis for direct comparison between the devices.Information about the test setup and the implementation of the measurements can be found here!In result of the measurements must be noted that the technical datas on the nameplate and the measured performance data in parts considerably deviate of each other. The measurement results are summarized in the following table. The device names specified in the tables are made anonymous by the testing laboratory.From the perspective of the testing laboratory, the results indicate that is urgent need to catch up  to make legislative requirements for performance measurements.A uniform implementation of the measurements should be the basis for the comparability of technical datas from different manufacturers. Thus, ultimately to provide the basis for trust in the performance specifications on name plates.  Only if the performance datas match the real achievable cooling capacities  the final customer is able to reach the technical cooling task in the required quality and reliable implementation.


Your Request

Further Projects

Image

Software for technical building equipment

Design cooling load and energetic annual simulation (VDI 2078, VDI 6007, VDI 6020)

Image

Measurements on ceiling mounted cooling systems

Comparative performance measurement