Current research projects

Image Measurements on ceiling mounted cooling systems
Image Performance tests of condensing units
Image Energy efficiency consulting - cogeneration systems
Image Brine (water)-water heat pump
Image Combined building and system simulation
Image Low Temperature Tribology
Image Innovative Parahydrogen Generator Based on Magnets
Image Calibration of Low Temperature Sensors
Image Thermostatic Expansion Valves
Image ZeroHeatPump
Image Certifiable connection types in cryogenics
Image Cryogenic liquid piston pumps for cold liquefied gases like LIN, LOX, LHe, LH2, LNG, LAr
Image Influenced melting point of water by magnetic field
Image Test method for high - temperature heat pump - oils
Image Innovative small helium liquefier
Image Solar Cooling

You are here:   /  Home


Humidifier System for High-Purity Gases

Industry and Research Instituts

Moritz Kuhn

+49-351-4081-5120

Nafion - moisture transfer

At the ILK Dresden a humidification system was developed and manufactured which is especially suitable for research facilities where very low dew point temperatures have to be adjusted and at the same time a high gas purity has to be guaranteed. The core component is a PermaPure® humidifier with Nafion® moisture exchange. The humidification system precisely controls the dew point via a bypass mixing with dry gas and also takes over the automatic filling of evacuated containers. The control system is optimised to prevent recondensation. Humidification can be controlled from any plant system via an interface. Table 1 shows the technical data of a humidification system for the humidification of synthetic air realized for the KIT in Karlsruhe. The system can be adapted for other applications, and all parameters can be adjusted to the respective requirements.

Table  1: Technical Data Humidifier System
Parameter Value
setpoint gas flow 750 litre/min
maximum relative humidity 95%
minimum dew point -60°C / -76°F
degree of gas purity 5.0
gas purity, number of particle < 5 particle/cm³