Current research projects

Image Industry 4.0 membrane heat and mass exchanger (i-MWÜ4.0)
Image Swirl-free on the move...
Image Software for technical building equipment
Image Reducing the filling quantity
Image Overall System Optimization of Refrigeration Plant Systems for Energy Transition and Climate Protection
Image CFE-Test of Cooker Hoods
Image Low Temperature Measuring Service
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image Micro heat exchangers in refrigeration
Image Measurement of insulated packaging
Image Panel with indirect evaporative cooling via membrane
Image Electrochemical decontamination of electrically conducting surfaces „EDeKo II“
Image IO-Scan - Integral measuring optical scanning method
Image Behavior of multiphase cryogenic fluids
Image Filter Tests
Image Mass Spectrometer

You are here:   /  Home


Humidifier System for High-Purity Gases

Industry and Research Instituts

Moritz Kuhn

+49-351-4081-5120

Nafion - moisture transfer

At the ILK Dresden a humidification system was developed and manufactured which is especially suitable for research facilities where very low dew point temperatures have to be adjusted and at the same time a high gas purity has to be guaranteed. The core component is a PermaPure® humidifier with Nafion® moisture exchange. The humidification system precisely controls the dew point via a bypass mixing with dry gas and also takes over the automatic filling of evacuated containers. The control system is optimised to prevent recondensation. Humidification can be controlled from any plant system via an interface. Table 1 shows the technical data of a humidification system for the humidification of synthetic air realized for the KIT in Karlsruhe. The system can be adapted for other applications, and all parameters can be adjusted to the respective requirements.

Table  1: Technical Data Humidifier System
Parameter Value
setpoint gas flow 750 litre/min
maximum relative humidity 95%
minimum dew point -60°C / -76°F
degree of gas purity 5.0
gas purity, number of particle < 5 particle/cm³

Your Request