Current research projects

Image Air-flow test rig for fan characteristic measurement
Image Corrosion inhibitor for ammonia absorption systems
Image Micro heat exchangers in refrigeration
Image Ice Slurry Generation
Image Low noise and non metallic liquid-helium cryostat
Image Computational fluid dynamics CFD
Image CFE-Test of Cooker Hoods
Image Swirl-free on the move...
Image Thermostatic Expansion Valves
Image All-in-one device for freeze-drying and production of biomaterial
Image Range of services laboratory analyses
Image Laseroptical measurement
Image Multifunctional electronic modules for cryogenic applications
Image Innovative Parahydrogen Generator Based on Magnets
Image Development of a Cryogenic Magnetic Air Separation Unit
Image Hybrid- Fluid for CO2-Sublimation Cycle

You are here:  Home /  Measurements and Tests


Testing of mobile leak detectors according to DIN EN 14624

auf Anfrage

Dipl.-Ing. (FH) René Seidel

+49-351-4081-5428

Performance test according to standard

Determination of the performance of mobile leak detectors

According to Regulation (EU) No. 517/2014, systems containing fluorinated greenhouse gases must be tested for leaks at regular intervals (varying between 6 months and 2 years) depending on the CO2 equivalent. In practice, mobile leak detectors are mainly used for this purpose.

To ensure the proper functioning of the equipment, Regulation (EC) 1516/2007 requires that refrigeration and air conditioning equipment and heat pumps with a charge > 3 kg of fluorinated greenhouse gases be tested for proper operation every 12 months. "The sensitivity of portable gas detection devices must be at least 5 g per year".

According to DIN EN 378-2 section 6.3.3.2, the detector must be calibrated at regular intervals according to the manufacturer's instructions.

The test procedure for at least annual inspections of the performance of mobile leak detectors and room monitors for halogenated refrigerants is described in DIN EN 14624.

For this check, use, for example, a testing device with a sliding or swiveling leak detector probe. The performance test includes:

  • static detection with detection limit
  • Response time
  • Cross sensitivity
  • dynamic detection limit
  • Detection limit with contaminated environment
  • Recovery time

For these tests, a test stand is available at the ILK Dresden on which mobile leak detectors can be tested for their performance.

To determine the performance, adjustable calibrated test leaks are filled with the appropriate test gases (e.g. R134a, R1234yf) and placed in the test stand. We would be pleased to perform this test for you. The test performed is certified with a test report. 

Please direct inquiries about testing mobile leak detectors with the appropriate test gases to the contact above.


Your Request

Further Projects - Measurements and Tests

Image

Preformance measurements of heat exchangers

Is the heat exchanger properly sized?

Image

Filter Tests

INDUSTRIAL AND LABORATORY PRECIPITATORS

Image

Investigation of coolants

Secondary loop refrigerants

Image

Refrigerants, lubricants and mixtures

Determination of working fluid properties