Current research projects

Image Tensile and compression testing
Image Tribological investigations of oil-refrigerant-material-systems
Image Service offer for Leak Detection and Tightness Test
Image Air-water heat pumps
Image Low noise and non metallic liquid-helium cryostat
Image Computational fluid dynamics CFD
Image Development of a Cryogenic Magnetic Air Separation Unit
Image Preformance measurements of heat exchangers
Image Laseroptical measurement
Image Heat2Power
Image CO₂ GAS HYDRATES FOR SUSTAINABLE ENERGY AND COOLING SOLUTIONS
Image Testzentrum PLWP at ILK Dresden
Image Ice Slurry Generation
Image Measurement of insulated packaging
Image Helium extraction from natural gas
Image Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K

You are here:  Home /  Research and Development


Calibration of Low Temperature Sensors

Industry and R&D

Dr. rer. nat. Matthias Schneider

+49-351-4081-5126

According to the comparative measurement method

Accurate and reliable measurements are the requirements for high-quality research and development or industrial production. Using the comparative measurement method the following sensors can be calibrated:

  • Resistance Temperature Detectors (RTD) with positive temperature coefficient (like Platinum or Rhodium-Iron RTDs)
  • RTD with negative temperature coefficient (like Germanium or Cernox™ RTDs)
  • Diode and thermocouples.

With an automatic measuring station several temperatures according to a sample point table will be adjusted. The calibration is carried out with secondary thermometers that are calibrated by an authority. Furthermore a fix point check with LHe or LN2 will be performed. In addition, a calbriated Cernox sensor is available for measurements in the low temperature range. The measuring facility allows the calibration of about 30 sensors at once. There are continuous extensions for different sensor types.

Parameter

IndicatorMinimalMaximal
Measuring range1.5 K350 K
Measuring accuracy5 mK (1.5 ... 4.2 K)50 mK (80 ... 350 K)
Sample dimensioncommon sensor packages
Sample preparationnot necessary

Your Request

Further Projects - Research and Development

Image

Electrical components in refrigeration circuits

High voltage tests under real conditions

Image

Influenced melting point of water by magnetic field

Controlled sub-cooling of products in freezing processes

Image

Non- invasive flow measurements

PDPA - flow fields and particle sizes

Image

Computational fluid dynamics CFD

Scientific analysis of flows