Current research projects

Image Computational fluid dynamics CFD
Image Optimizing HVAC operation with machine learning
Image Overall System Optimization of Refrigeration Plant Systems for Energy Transition and Climate Protection
Image Thermostatic Expansion Valves
Image ZeroHeatPump
Image Investigation of coolants
Image Software modules
Image Test method for high - temperature heat pump - oils
Image Modular storage system for solar cooling
Image Multifunctional electronic modules for cryogenic applications
Image Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K
Image Range of services laboratory analyses
Image Industry 4.0 membrane heat and mass exchanger (i-MWÜ4.0)
Image Cryogenic liquid piston pumps for cold liquefied gases like LIN, LOX, LHe, LH2, LNG, LAr
Image Tribological investigations of oil-refrigerant-material-systems
Image Swirl-free on the move...

You are here:   /  Home


Investigation according to DIN EN ISO 14903

Dipl.-Ing. (FH) René Seidel

+49-351-4081-5428

These tests according to DIN EN ISO 14903 are possible at ILK Dresden

§7.4 Tightness Test

§7.6 Pressure- Temperature- Vibration Test

§7.7 Simulation Operating

§7.8 Freezing Test

§7.9 Pressure Test

§7.10 Vacuum Test

§7.11 Compatibility Test

§7.12 Fatigue Test

 

§7.4 Tightness Test

  • Tightness control according to classification in DIN EN ISO 14903 at room temperature
  • In each case per connection or component (test sample) before and after the respective modules
  • Permissible leakage rate (helium) depending on the selected tightness control level E.g. A1 with Q ≤ 7,5E-7 Pa m³/s = 7,5E-6 mbar l/s @ 10 bar rel., 20 °C

  • Testing with helium gas detector in vacuum method or substitute method

  • Procedure section 10 according to DIN EN 13185, Detection limit 5,0E-13 Pa m³/s helium

  • Test gas helium

§7.6 PTV Test and if necessary §7.7 Simulation Operating

  • Tmin: -40 °C (specified by the customer)
  • Tmax: +140 °C (specified by the customer)
  • Test pressure PSmax: 100 bar rel. (specified by the customer)
  • 50 Temperature changes
  • 200 Pressure pulses
  • Subsequent vibration test < 200 Hz, 1 Axis, 2 Mio vibrations, const. amplitude
  • Simulation Operating, E.g. 25x open and close the connection

§7.8 Freezing Test

  • Freezing test in a vacuum test chamber. The test specimen is exposed in a vacuum chamber filled with water at 500 mbar abs (+ 0, -100 mbar) for at least 10 min. The pressure is then increased to atmospheric pressure.

  • Afterward, the test specimens are stored at -15 °C (or below) for at least 30 min in a temperature-controlled cabinet and then exposed to water at ambient temperature for at least 5 min., these steps are repeated a total of 30 times

§7.9 Pressure Test

  • The pressure test is performed at 5xPS for 1 minute
  • Medium oil

§7.10 Vacuum Test

  • The test samples are subjected to the test to confirm that they are able to withstand a vacuum with an absolute pressure of 6.5 kPa for 1 h without leakage.
  • For this purpose, the pressure is monitored and it is checked whether the pressure increase Δp after 1 h is less than 0.2 kPa. The effect of the temperature change on the pressure is taken into account.

§7.11 Compatibility Test

  • Investigation into the chemical compatibility of the materials

  • Aging for 336 h at 50 °C in refrigerant-oil atmosphere (for elastomer materials)

  • Aging for 1000 h at 50 °C in refrigerant-oil atmosphere (for thermoplastic materials)

  • Determination of mass, volume and hardness before and after aging

§7.12 Fatigue Test

  • Fatigue test, 250.000 Pressure cycles at max. 50 changes per minute

  • Test range between test pressure PS and atmospheric pressure, test medium: water


Your Request

Further Projects

Image

Intelligent innovative power supply for superconducting coils

Compact, powerful power supply with 4-quadrant converter

Image

Laseroptical measurement

PIV and LDA / PDA

Image

Multifunctional electronic modules for cryogenic applications

Electronic with less wiring effort - more than 100 sensors via one feedthrough

Image

Certifiable connection types in cryogenics

Detachable and permanent connections, adhesive bond / form closure / force closure

Image

Combined building and system simulation

Scientific analysis of thermodynamic processes in buildings and its systems