Current research projects

Image Innovative Manufacturing Technologies for Cryosorption Systems
Image Verification of storage suitability of cryo tubes
Image Performance tests of refrigerant compressors
Image Solar Cooling
Image Filter Tests
Image Test procedures for electrical components
Image Micro fluidic expansion valve
Image Non- invasive flow measurements
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image ZeroHeatPump
Image Pulse-Tube-Refrigerator with sealed compressor
Image Test rigs for refrigeration and heat pump technology
Image Low Temperature Tribology
Image CFE-Test of Cooker Hoods
Image Micro heat exchangers in refrigeration
Image Test method for high - temperature heat pump - oils

You are here:  Home /  Research and Development


Calibration of Low Temperature Sensors

Industry and R&D

Dr. rer. nat. Matthias Schneider

+49-351-4081-5126

According to the comparative measurement method

Accurate and reliable measurements are the requirements for high-quality research and development or industrial production. Using the comparative measurement method the following sensors can be calibrated:

  • Resistance Temperature Detectors (RTD) with positive temperature coefficient (like Platinum or Rhodium-Iron RTDs)
  • RTD with negative temperature coefficient (like Germanium or Cernox™ RTDs)
  • Diode and thermocouples.

With an automatic measuring station several temperatures according to a sample point table will be adjusted. The calibration is carried out with secondary thermometers that are calibrated by an authority. Furthermore a fix point check with LHe or LN2 will be performed. In addition, a calbriated Cernox sensor is available for measurements in the low temperature range. The measuring facility allows the calibration of about 30 sensors at once. There are continuous extensions for different sensor types.

Parameter

IndicatorMinimalMaximal
Measuring range1.5 K350 K
Measuring accuracy5 mK (1.5 ... 4.2 K)50 mK (80 ... 350 K)
Sample dimensioncommon sensor packages
Sample preparationnot necessary

Your Request

Further Projects - Research and Development

Image

Micro fluidic expansion valve

for increasing of the efficiency of small and compact cooling units

Image

Hydrogen and methane testing field at the ILK

Simultaneously pressures up to 1,000 bar, temperatures down to –253°C

Image

Low noise and non metallic liquid-helium cryostat

Low-noise Magnetic Field Cryostat for SQUID-Applications

Image

Cryostats, Non-Metallic and Metallic

position indenpendent, highest endurance, tiltable for liquid helium and liquid nitrogen