Current research projects

Image Lifetime prediction of hermetic compressor systems
Image Investigation of material-dependent parameters
Image Development of test methods and test rigs for stationary integrated refrigeration units
Image Modular storage system for solar cooling
Image Investigation of materials
Image CO₂ GAS HYDRATES FOR SUSTAINABLE ENERGY AND COOLING SOLUTIONS
Image Testzentrum PLWP at ILK Dresden
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image Pulse-Tube-Refrigerator with sealed compressor
Image Brine (water)-water heat pump
Image Test rigs for refrigeration and heat pump technology
Image IO-Scan - Integral measuring optical scanning method
Image Combined building and system simulation
Image Intelligent innovative power supply for superconducting coils
Image All-in-one device for freeze-drying and production of biomaterial
Image In-Situ-Swelling Behaviour of Polymer Materials in Flammable Fluids

You are here:   /  Home


Calibration of Low Temperature Sensors

Industry and R&D

Dr. rer. nat. Matthias Schneider

+49-351-4081-5126

According to the comparative measurement method

Accurate and reliable measurements are the requirements for high-quality research and development or industrial production. Using the comparative measurement method the following sensors can be calibrated:

  • Resistance Temperature Detectors (RTD) with positive temperature coefficient (like Platinum or Rhodium-Iron RTDs)
  • RTD with negative temperature coefficient (like Germanium or Cernox™ RTDs)
  • Diode and thermocouples.

With an automatic measuring station several temperatures according to a sample point table will be adjusted. The calibration is carried out with secondary thermometers that are calibrated by an authority. Furthermore a fix point check with LHe or LN2 will be performed. In addition, a calbriated Cernox sensor is available for measurements in the low temperature range. The measuring facility allows the calibration of about 30 sensors at once. There are continuous extensions for different sensor types.

Parameter

IndicatorMinimalMaximal
Measuring range1.5 K350 K
Measuring accuracy5 mK (1.5 ... 4.2 K)50 mK (80 ... 350 K)
Sample dimensioncommon sensor packages
Sample preparationnot necessary

Your Request

Further Projects

Image

Tensile and compression testing

Determination of yield strength, tensile strength and elongation at break

Image

Investigation of material-dependent parameters

Investigation of the permeation behavior

Image

Cool Up

Upscaling Sustainable Cooling

Image

Breakthrough Sensor for Adsorption Filters (BelA)

Sensor system for detecting an imminent breakthrough in gas filtration

Image

Ionocaloric cooling

Ionocaloric solid-liquid phase cooling process