Current research projects

Image 3D - Air flow sensor
Image Mass Spectrometer
Image Humidifier System for High-Purity Gases
Image Intelligent innovative power supply for superconducting coils
Image Electrical components in refrigeration circuits
Image CFE-Test of Cooker Hoods
Image High temperature heat pump
Image Innovative Parahydrogen Generator Based on Magnets
Image Investigation of coolants
Image Overall System Optimization of Refrigeration Plant Systems for Energy Transition and Climate Protection
Image Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K
Image Pulse-Tube-Refrigerator with sealed compressor
Image Test procedures for electrical components
Image Investigation of material-dependent parameters
Image Ice Slurry Generation
Image Non- invasive flow measurements

You are here:   /  Home


Testing of mobile leak detectors according to DIN EN 14624

auf Anfrage

Dipl.-Ing. (FH) René Seidel

+49-351-4081-5428

Performance test according to standard

Determination of the performance of mobile leak detectors

According to Regulation (EU) No. 517/2014, systems containing fluorinated greenhouse gases must be tested for leaks at regular intervals (varying between 6 months and 2 years) depending on the CO2 equivalent. In practice, mobile leak detectors are mainly used for this purpose.

To ensure the proper functioning of the equipment, Regulation (EC) 1516/2007 requires that refrigeration and air conditioning equipment and heat pumps with a charge > 3 kg of fluorinated greenhouse gases be tested for proper operation every 12 months. "The sensitivity of portable gas detection devices must be at least 5 g per year".

According to DIN EN 378-2 section 6.3.3.2, the detector must be calibrated at regular intervals according to the manufacturer's instructions.

The test procedure for at least annual inspections of the performance of mobile leak detectors and room monitors for halogenated refrigerants is described in DIN EN 14624.

For this check, use, for example, a testing device with a sliding or swiveling leak detector probe. The performance test includes:

  • static detection with detection limit
  • Response time
  • Cross sensitivity
  • dynamic detection limit
  • Detection limit with contaminated environment
  • Recovery time

For these tests, a test stand is available at the ILK Dresden on which mobile leak detectors can be tested for their performance.

To determine the performance, adjustable calibrated test leaks are filled with the appropriate test gases (e.g. R134a, R1234yf) and placed in the test stand. We would be pleased to perform this test for you. The test performed is certified with a test report. 

Please direct inquiries about testing mobile leak detectors with the appropriate test gases to the contact above.


Your Request

Further Projects

Image

Low Temperature Measuring Service

Measurement of Thermal Properties at Low Temperatures

Image

Practical training, diploma, master, bachelor

Student training - Education at ILK

Image

Test procedures for electrical components

Insulating properties of hermetic compressors

Image

3D - Air flow sensor

Anemometer for determination of 3d-air flow