Aktuelle Forschungsprojekte

Image Performance tests of refrigerant compressors
Image Investigation of coolants
Image Practical training, diploma, master, bachelor
Image Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K
Image Investigation according to DIN EN ISO 14903
Image Ice Slurry Generation
Image Testing of mobile leak detectors according to DIN EN 14624
Image Measurements on ceiling mounted cooling systems
Image All-in-one device for freeze-drying and production of biomaterial
Image Humidifier System for High-Purity Gases
Image Micro heat exchangers in refrigeration
Image IO-Scan - Integral measuring optical scanning method
Image IN-SITU SWELLING BEHAVIOUR OF POLYMER MATERIALS IN FLAMMABLE FLUIDS
Image Innovative small helium liquefier
Image Tribological investigations of oil-refrigerant-material-systems
Image Lifetime prediction of hermetic compressor systems

You are here:  Home /  Measurements and Tests


Development of test methods and test rigs for stationary integrated refrigeration units

BMWi Euronorm Innokom

02/2017 – 07/2019

Andreas Peusch

+49-351-4081-5221

How efficient is my refrigeration unit?

The objective of the R&D project was the development of a test method for stationary integrated refrigeration units. The test method comprises different device variants, like ceiling mounted, wall mounted or split refrigeration units. The method provides reliable performance data and thus enables a manufacturer-independent efficiency comparison.

Measurements in the 3- or 4-chamber measurement setup were carried out using the calorimeter method with compensation of the ambient conditions. This enabled the measurements of devices with low cooling capacity (0.5 - 4 kW).

In the selected test setup (Figure 1), the cooling capacity is measured indirectly via an electrical power of the compensation heating. To determine the total cooling capacity, the heat input into the calorimeter room and, if necessary, internal loads (sensible and latent heat) have to be added together.

The test method comprises following features:

  • Suitable for low temperature devices (-20 °C) and normal temperature cooling (0 °C)
  • Measurement in the calorimeter room (3- or 4-zone concept)
  • Determination of heat input via enclosure surfaces before power measurement
  • Establishment of equilibrium conditions (settling phase) of the temperatures to be set (up to 24 h)
  • Measuring period up to 6 h with permissible tolerance band of 0.2 K

Conclusion:

  • Results were included in new test standard prEN 17432
  • Establishment of a uniform Europe-wide comparison criterion
  • Performance and efficiency data on a uniform basis leads to higher confidence and thus also to lower consumption costs

Your Request

Further Projects - Measurements and Tests