Aktuelle Forschungsprojekte

Image High temperature heat pump
Image Ionocaloric cooling
Image Lifetime prediction of hermetic compressor systems
Image Micro heat exchangers in refrigeration
Image Filter Tests
Image Air-flow test rig for fan characteristic measurement
Image Innovative Parahydrogen Generator Based on Magnets
Image Optimizing HVAC operation with machine learning
Image Pulse-Tube-Refrigerator with sealed compressor
Image Calibration of Low Temperature Sensors
Image Software for test rigs
Image Energy efficiency consulting - cogeneration systems
Image Electrochemical decontamination of electrically conducting surfaces „EDeKo II“
Image Industry 4.0 membrane heat and mass exchanger (i-MWÜ4.0)
Image Characterisation of Superconductors in Hydrogen Atmosphere
Image 3D - Air flow sensor

You are here:  Home /  Research and Development


Development of test methods and test rigs for stationary integrated refrigeration units

BMWi Euronorm Innokom

02/2017 – 07/2019

Andreas Peusch

+49-351-4081-5221

How efficient is my refrigeration unit?

The objective of the R&D project was the development of a test method for stationary integrated refrigeration units. The test method comprises different device variants, like ceiling mounted, wall mounted or split refrigeration units. The method provides reliable performance data and thus enables a manufacturer-independent efficiency comparison.

Measurements in the 3- or 4-chamber measurement setup were carried out using the calorimeter method with compensation of the ambient conditions. This enabled the measurements of devices with low cooling capacity (0.5 - 4 kW).

In the selected test setup (Figure 1), the cooling capacity is measured indirectly via an electrical power of the compensation heating. To determine the total cooling capacity, the heat input into the calorimeter room and, if necessary, internal loads (sensible and latent heat) have to be added together.

The test method comprises following features:

  • Suitable for low temperature devices (-20 °C) and normal temperature cooling (0 °C)
  • Measurement in the calorimeter room (3- or 4-zone concept)
  • Determination of heat input via enclosure surfaces before power measurement
  • Establishment of equilibrium conditions (settling phase) of the temperatures to be set (up to 24 h)
  • Measuring period up to 6 h with permissible tolerance band of 0.2 K

Conclusion:

  • Results were included in new test standard prEN 17432
  • Establishment of a uniform Europe-wide comparison criterion
  • Performance and efficiency data on a uniform basis leads to higher confidence and thus also to lower consumption costs

Your Request

Further Projects - Research and Development

Image

Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K

high performance efficiency, environmental friendliness, compactness, cost-effectiveness

Image

Intelligent innovative power supply for superconducting coils

Compact, powerful power supply with 4-quadrant converter

Image

Laseroptical measurement

PIV and LDA / PDA

Image

Multifunctional electronic modules for cryogenic applications

Electronic with less wiring effort - more than 100 sensors via one feedthrough

Image

Certifiable connection types in cryogenics

Detachable and permanent connections, adhesive bond / form closure / force closure