Current research projects

Image Low noise and non metallic liquid-helium cryostat
Image Electrical components in refrigeration circuits
Image Practical training, diploma, master, bachelor
Image Helium extraction from natural gas
Image Investigation of materials
Image Thermostatic Expansion Valves
Image High Capacity Pulse Tube Cooler
Image High temperature heat pump
Image Mass Spectrometer
Image Characterisation of Superconductors in Hydrogen Atmosphere
Image Performance tests of refrigerant compressors
Image Modular storage system for solar cooling
Image In-Situ-Swelling Behaviour of Polymer Materials in Flammable Fluids
Image Certification of efficient air conditioning and ventilation systems through the new "indoor air quality seal" for non-residential buildings
Image Service offer for Leak Detection and Tightness Test
Image Investigation according to DIN EN ISO 14903

You are here:  Home /  Measurements and Tests


Testing of mobile leak detectors according to DIN EN 14624

auf Anfrage

Dipl.-Ing. (FH) René Seidel

+49-351-4081-5428

Performance test according to standard

Determination of the performance of mobile leak detectors

According to Regulation (EU) No. 517/2014, systems containing fluorinated greenhouse gases must be tested for leaks at regular intervals (varying between 6 months and 2 years) depending on the CO2 equivalent. In practice, mobile leak detectors are mainly used for this purpose.

To ensure the proper functioning of the equipment, Regulation (EC) 1516/2007 requires that refrigeration and air conditioning equipment and heat pumps with a charge > 3 kg of fluorinated greenhouse gases be tested for proper operation every 12 months. "The sensitivity of portable gas detection devices must be at least 5 g per year".

According to DIN EN 378-2 section 6.3.3.2, the detector must be calibrated at regular intervals according to the manufacturer's instructions.

The test procedure for at least annual inspections of the performance of mobile leak detectors and room monitors for halogenated refrigerants is described in DIN EN 14624.

For this check, use, for example, a testing device with a sliding or swiveling leak detector probe. The performance test includes:

  • static detection with detection limit
  • Response time
  • Cross sensitivity
  • dynamic detection limit
  • Detection limit with contaminated environment
  • Recovery time

For these tests, a test stand is available at the ILK Dresden on which mobile leak detectors can be tested for their performance.

To determine the performance, adjustable calibrated test leaks are filled with the appropriate test gases (e.g. R134a, R1234yf) and placed in the test stand. We would be pleased to perform this test for you. The test performed is certified with a test report. 

Please direct inquiries about testing mobile leak detectors with the appropriate test gases to the contact above.


Your Request

Further Projects - Measurements and Tests

Image

Measurements on ceiling mounted cooling systems

Comparative performance measurement

Image

Solar Cooling

Solar Cooling with Photovoltaic

Image

Hydrogen and methane testing field at the ILK

Simultaneously pressures up to 1,000 bar, temperatures down to –253°C

Image

Calibration of Low Temperature Sensors

According to the comparative measurement method

Image

Low Temperature Measuring Service

Measurement of Thermal Properties at Low Temperatures