Current research projects

Image Thermostatic Expansion Valves
Image Laseroptical measurement
Image Non- invasive flow measurements
Image Intelligent innovative power supply for superconducting coils
Image Cryogenic liquid piston pumps for cold liquefied gases like LIN, LOX, LHe, LH2, LNG, LAr
Image Energy efficiency consulting - cogeneration systems
Image Influenced melting point of water by magnetic field
Image Air-water heat pumps
Image Heat2Power
Image Innovative small helium liquefier
Image Overall System Optimization of Refrigeration Plant Systems for Energy Transition and Climate Protection
Image Air-flow test rig for fan characteristic measurement
Image Calibration leak for the water bath leak test
Image Certification of efficient air conditioning and ventilation systems through the new "indoor air quality seal" for non-residential buildings
Image 3D - Air flow sensor
Image Testzentrum PLWP at ILK Dresden

You are here:   /  Home


Pulse-Tube-Refrigerator with sealed compressor

Federal Ministry of Economics and Energy

Dipl.-Ing. Gunar Schroeder

+49-351-4081-5129

for mobil use in the hydrogen technology

Within the research project "Mobile single-stage pulse tube cooler with hermetic compressor drive" (project number MF 130012), a compact, robust and low-maintenance cryocooler was developed.
Possible applications for this cryocooler, e.g.,

  • Cooling of mobile high-pressure tanks for storing fuels in cryogenic liquid or supercritical state (e. g. H2 – cryogenic under high pressure)
  • mobile cooling applications < –40°C in medical technology, transport of organic material or samples

The system has a simple and cost-effective design with the following advantages:

  • Mobile use, supply voltage 12 V or 24 V, air-cooled
  • Supply of cryogenic temperatures in the range 60...120 K
  • Low maintenance and long-life, no moving parts in the cold part
  • Programmable temperature curves via microcontroller-based control
  • Low power consumption, in the range of 500 W
  • Low space requirement, arrangement can be adapted
  • Lower costs control through extensive use of commercial components

Figure 1 shows the experimental setup of the cryocooler in a specially adapted orifice double inlet configuration. With the use of a special valve control, 2 W cooling capacity at 77 K and 5 W at 90 K could be achieved. The lowest temperature reached with this single-stage configuration was 68 K. The temperature stability of the system was validated in a test lasting 100 h, see figure 2. In further investigations with a specially adapted compressor, even lower temperatures are to be achieved, down to 40 K.

We are looking for industrial partners for adaptations for special application purposes or possible further developments. Conceivable are, for example, a compact system suitable for use in motor vehicles in a functional housing with the necessary interfaces or a further development of the current cooler to achieve higher cooling capacity, lower temperatures and higher efficiency.


Your Request

Further Projects

Image

Performance tests of refrigerant compressors

Does your compressor perform well?

Image

Swirl-free on the move...

...with a contra-rotating fan

Image

Measurement of insulated packaging

How efficient is my cool box?

Image

Hybrid- Fluid for CO2-Sublimation Cycle

Cryogenic cooling by CO2 sublimation

Image

Energy efficiency consulting - cogeneration systems

How efficient is my refrigeration system?