Current research projects

Image Service offer for Leak Detection and Tightness Test
Image Test procedures for electrical components
Image Swirl-free on the move...
Image All-in-one device for freeze-drying and production of biomaterial
Image Development of a Cryogenic Magnetic Air Separation Unit
Image Development of test methods and test rigs for stationary integrated refrigeration units
Image Modular storage system for solar cooling
Image Verification of storage suitability of cryo tubes
Image Test rigs for refrigeration and heat pump technology
Image Range of services laboratory analyses
Image Non- invasive flow measurements
Image Reduction of primary noise sources of fans
Image Testing of mobile leak detectors according to DIN EN 14624
Image Micro fluidic expansion valve
Image Performance tests of condensing units
Image Electrochemical decontamination of electrically conducting surfaces „EDeKo II“

You are here:  Home /  Research and Development


Reducing the filling quantity

BMWi EuroNorm INNO-KOM

03/2019-06/2021

K. Bratanitsch

+49-351-4081-5212

How much refrigerant must be filled?

Due to the F-gas regulation of the EU, synthetic refrigerants are becoming increasingly expensive and more difficult to obtain. The synthetic and partly natural substitute refrigerants are often flammable or toxic. The remaining synthetic refrigerants with low hazard potential are becoming more and more expensive and some of them still have a significant global warming potential. For this reason, it makes sense to keep the filling quantity of all new refrigeration systems as low as possible. Historically, refrigeration plants have usually been built without much consideration for the filling quantity of the plant. Often even large collectors were installed in order to always have a sufficient filling quantity without exact calculation and to compensate for the loss of refrigerant between the service intervals.

In this project, possible actions are investigated, which lead to significant reductions in refrigerant filling quantities already in the design and construction phase. In particular, the necessity and size of refrigerant receivers will be investigated. Except for a refrigerant receiver, the largest refrigerant quantities are found in the heat exchangers of the refrigeration cycle, i.e. in the condenser up to 50 % (according to other literature sources even up to 65 %) and in the evaporator up to 25 %. As a result, very strong levers for reducing the refrigerant charge can be seen in these components. Therefore, the necessary filling quantity of different heat exchangers should be examined and measured in detail. Thereby classical tube-fin, microchannel and plate heat exchangers shall be investigated.

As a result of the project, a new method is to be developed which takes into account a maximum possible reduction of the refrigerant charge quantity from the outset when planning and designing a refrigeration system.

Based on the first results and previous experience we can offer calculations of the filling quantity. Furthermore, a program for calculating the filling quantity is in preparation.

 


Your Request

Further Projects - Research and Development

Image

High Capacity Pulse Tube Cooler

for Cryogenic High-Power Applications

Image

Thermal engines

Power Generation from Waste Heat

Image

Helium extraction from natural gas

Innovative solutions for helium extraction

Image

Ice Slurry Generation

Using Direct Evaporation

Image

Pulse-Tube-Refrigerator with sealed compressor

for mobil use in the hydrogen technology